ARAN VISION logo

ARAN VISION

Product specification sheet

150-C201NBDDocument: AV-FEED-XUMFF3
Industrial controller Allen-Bradley model 150-C201NBD,  Part number 150-C201NBD

Allen-Bradley · PLC and HMI

Industrial controller Allen-Bradley model 150-C201NBD

Industrial controller Allen-Bradley part number 150-C201NBD; Conventional thermal current (Ith): TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts; Delta connected motor current: 116...348A @ 380/400/415/460V AC, 3-phase; Delta connected motor power, max: 75...125Hp @ 230V AC, 60 Hz, 3-phase. Technical specifications, condition and supply feasibility are checked before ordering.

Manufacturer part number
150-C201NBD
Brand
Allen-Bradley
Category
PLC and HMI
Catalog status
Available on request

Technical specifications

Lifecycle Status
Active
Repair Options Available
Yes
Sub Brand
SMC-3
Altitude
2000 m
Break
TB-97, -98 (OVLD/Fault): 72VA for auxiliary contacts
Cable size
0.2...2.5 mm2 (24...14 AWG) for control terminals
Controller type
SMC-3
Conventional thermal current (Ith)
TB-97, -98 (OVLD/Fault): 1 A for auxiliary contacts
Degree of protection (IP)
IP2X
Delta connected motor current
116...348A @ 380/400/415/460V AC, 3-phase
Delta connected motor power, max
75...125Hp @ 230V AC, 60 Hz, 3-phase
Depth
265.3 mm (10.45 in)
Dielectric withstand
2500V AC per IEC for power circuit
DV/DT protection
1000V/µs for power circuit
EMC emission levels
Radiated emission: Class A per IEC
EMC immunity levels
Surge transient: per EN/IEC 60947-4-2 per IEC
Enclosure
Open type
Fan power rating
40 VA
Role
Single direction
Height
560 mm (22.05 in)
High capacity available fault current, max
70kA @ 600V, maximum current 600 A time delay Class J or Class L fuse for inside delta connected motors
Humidity
5...95% noncondensing
Input OFF-state current
<10 mA, <12 mA @ input OFF-state voltage (IN1, IN2) for control circuit
Input OFF-state voltage (IN1, IN2), max
40V AC @ 17V DC/12V AC for control circuit
Input ON-state current (IN1, IN2)
9.8mA @ 120V AC/19.6mA @ 240V AC for control circuit, 7.3mA @ 24V AC/DC for control circuit
Input ON-state voltage, during start (IN1, IN2)
85V AC @ 19.2V DC/19.2V AC minimum for control circuit
Insulation voltage
Rated 600V AC per UL/CSA/NEMA for power circuit
Integrated motor overload protection
true
Internal bypass
true
Line connected motor current
67...201A @ 380/400/415/460V AC, 3-phase
Line connected motor power, max
95...110 kW @ 380/400/415V AC @ 50Hz, 3-phase
Make
TB-97, -98 (OVLD/Fault): 432VA for auxiliary contacts
Mounting hole size
11.5 mm
Number of contacts
TB-97, -98 (OVLD/Fault): 1 for auxiliary contacts
Number of poles
Equipment is designed for 3-phase only for power circuit
Operating frequency
50/60 Hz per UL/CSA/NEMA for power circuit

This sheet provides a quick technical summary. For design, installation and final selection, review the latest official manufacturer documentation and verify the complete part number.